Back

GasGuard Manual - Interlock System

GasGuard Manual - Interlock System

The GasGuard Manual Kitchen Interlock is designed to meet the requirements IGEM/UP/19 and BS6173:2009 (where all appliances are fitted with Flame Failure Devices), with numerous additional safety features added based on our 35 years of experience in the industry.

This cost effective non-proving system combines unrivalled functionality with the same user friendly interface as all Flamefast systems. With individual alarm indications for external devices and a dedicated engineers button, diagnosis of any site issues can be done quickly and hassle free.

Downloads

View FileGASGUARD Manual - Interlock System
  • No commissioning required
  • 24VDC auxiliary power output
  • Interfaces for Gas Sensors & CO2 Monitors, Ventilation Interlocks, Building Management Systems (BMS), Remote Emergency Stop Buttons and Fire Alarm Systems
  • Built in time delays to avoid nuisance tripping
  • Engineers Mode for easy fault diagnosis
  • UK MANUFACTURED

Installer Selectable Options

  • Gas Availability Timer (1-15 Hours or Constant)
  • 2x 0-10V Inputs (Preset programs)

Dimensions

  • Height 180 mm
  • Width 130 mm / 140 mm Including Hinge
  • Depth 60 mm / 85 mm Including Stop Button

Technical Specification

  • Power Supply 230VAC
  • Power Output (Gas Solenoid) 230VAC
  • IP Rating IP65 (Providing rear entry sealed)
  • Approval CE

Basic Operation

When switched on via the key switch the GasGuard Manual system provides gas to the kitchen and monitors all external interfaces such as ventilation systems.
Upon receiving a fault signal from any external devices, the GasGuard will ensure that the gas is isolated to prevent any potential issues.
The easy to use engineers button can be used to display any faults with the system and allow gas through for commissioning and purging.

External Device Interfaces

  • BMS Volt Free Contact (Valve Status) – Rated 230V 5A Max
  • 24V Out Auxiliary Power Supply (170mA Max) (to be used for Gas Sensors, Transmitters etc.)
  • Gas Sensor 24V Signal to monitor external VFC
  • Ventilation 24V Signal to monitor external VFC
  • Remote Stop 24V Signal to monitor external VFC
  • Fire Alarm 24V Signal to monitor external VFC
  • 2x 0-10V In Monitors external devices providing a 0-10V signal (programs preset – see Wiring Diagram for details)

View our Gas Safety Solutions

View our Gas Safety Solutions

Not sure what you need?

Not sure what you need?

Ask one of our Experts

Ask one of our Experts

Call us on... 01925 281 230