GasMonitor

The GasMonitor is a low cost high specification 16 channel gas detection panel designed for use with the Flamefast Gas sensor range.

Any combination of sensors from the FGS range can be connected by simply wiring in parallel, cutting down on installation costs. 

Top Key Features

  • 16 Channel Monitor
  • Clear LCD indication
  • Auto-reset following power failure
  • Fire Alarm test bypass timer
  • 24VDC auxiliary power output to power 4-6
  • UK Manufactured

Overview

The GasMonitor is a low cost high specification 16 channel gas detection panel designed for use with the Flamefast Gas sensor range.

Any combination of sensors from the FGS range can be connected by simply wiring in parallel, cutting down on installation costs. The communication interface allows all sensor information to be displayed on the panel, this includes gas type, concentration status, alarms and calibration data.

The relay outputs allow the unit to be connected to external systems or alarms beacons and the latching and failsafe facilities combined with the additional device interfaces offer the flexibility to cover any application. 

Key Features

  • 16 Channel Monitor
  • Clear LCD indication
  • Auto-reset following power failure
  • Fire Alarm test bypass timer
  • 24VDC auxiliary power output to power 4-6
  • Flamefast Gas Sensors dependant on sensor type
  • External power supply required for additional
  • Additional Interfaces for: Thermal Links, Ventilation Systems, Remote Emergency Stop Buttons and Fire Alarm Systems
  • Sensor calibration reminder
  • Alarm 1, Alarm 2 and Fault relays
  • Selectable relay latching function
  • 5 Year Warranty
  • UK MANUFACTURED

Dimensions

Height:180 mm
Width:180 mm
190 mm including hinge
Depth:60 mm

Basic Operation

The GasMonitor has three buttons on the front:
Reset - The GasMonitor Alarm 1 and 2 relays are activated depending on the sensor conditions. Once an alarm has cleared the reset button can be used to reset any relays that are set to latch this will also reset the Gas Valve output which will shut down if any sensor reaches Alarm 2.
Mute - If there are any gas alarms, this can be used to silence the panel for 10 minutes. If this is held in for 10 seconds, this will also reset any non-latching alarm relays for 2 minutes.
Test - The operation of the Test button is dependent on the panel status:

  • If the panel is live without any alarm conditions, holding this button in for 10 seconds will enable the Fire Alarm bypass. The Fire Alarm interface will be ignored for 30 minutes to allow tests to be carried out.
  • Following an alarm (prior to reset), holding the Test button for 5 seconds each will change the state of the Alarm 1, Alarm 2 and Fault relays.

Technical Specifications

Power Supply:100 - 250VAC 50/60Hz
Power Consumption:40W (Max)
Power Output:
Gas Solenoid: Switched Mains
Alarm 1: SPDT - 5A @ 250V Max
Alarm 2: SPDT - 5A @ 250V Max
Fault: SPDT - 5A @ 250V Max
IP Rating:IP65
Approval:CE, UKCA

External Device Interfaces

24V OutAuxiliary Supply (300mA Max) for FGS 
Gas SensorBACnet Interface for Gas Sensors
Ventilation24V Signal to monitor external VFC
Thermal Link24V Signal to monitor external VFC
Fire Alarm24V Signal to monitor external VFC
Remote Stop24V Signal to monitor external VFC

Installer Selectable Options

  • Energise relays (Failsafe)
  • Auto-reset
  • Alarm 1 Latching
  • Alarm 2 Latching

NEED THE REQUIREMENTS?

minReq-Kitchen

Commercial
Kitchens

arrow-kitchen
minReq-lab

Teaching
Areas

arrow-lab
minReq-plant

Plant 
Rooms

arrow-plant

Part Numbers & Options / Accessories

PART NODESCRIPTION
GM-P0GasMonitor Panel

Data Sheets

General specifications in .pdf format

Operation Manuals

Installation and Operation instruction in .pdf format

Coming Soon

BIM Files

CAD drawings in .rfa format

There are currently no videos available