Air DP Transmitter (ADPT)
The Flamefast multi-range ADPT provide a cost effect, compact solution for monitoring and controller pressure differentials in a wide range of ventilation applications, including monitoring filter degradation.
Top Key Features
- 13-27V AC/DC Supply
- User selectable 0-10V or 4-20mA output
- User selectable signal dampening
- 10 user selectable output scalings
- UK Manufactured
Overview
The Flamefast multi-range ADPT provide a cost effect, compact solution for monitoring and controller pressure differentials in a wide range of ventilation applications, including monitoring filter degradation.
With a user selectable 0-10V or 3 wire 4-20mA output, and 10 selectable output ranges, the ADPT provides unrivalled flexibility. The high accuracy sensing element, combined with the manual and auto zero functions, provide longterm stability for the life of the sensor.
The output signal dampening can be set at 0.3, 3.0 or 10 seconds, to iron out any spikes, or soften when low level filtering are required.
Key Features
- 13-27V AC/DC Supply
- User selectable 0-10V or 4-20mA output
- User selectable signal dampening
- 10 user selectable output scalings
- Compact design
- Duct kit included as standard
- Manual and Auto Calibration functions
- UK MANUFACTURED
Dimensions
| Height: | 104 mm |
|---|---|
| Width: | 790 mm |
| Depth: | 440 mm |
Technical Specifications
| Power Supply: | 13-27V AC/DC | ||||
|---|---|---|---|---|---|
| Power Consumption: | 50mA @ 24V Max | ||||
| Analogue Outputs: | 0-10V (3 Wire) or 4-20mA (3 Wire) | ||||
| Pressure Type: | Differential | ||||
| Sensor Type: | Piezo-resistive | ||||
| Overload Pressure: | 70kPa | ||||
| Accuracy: | <±3% FS | ||||
| Repeatability: | <±0.3% FS / Year | ||||
| Thermal Coefficient: | <±0.02% FS / °C | ||||
| Process Connections: | 6mm Male (5mm ID Hose) | ||||
| Operation Conditions: |
| ||||
| Body Material: | PC/ABS | ||||
| Media Temp: | -40 ~ 110°C | ||||
| IP Rating: | IP65 | ||||
| Colour: | Grey/Black | ||||
| Approval: | CE, UKCA |
Installer Selectable Options
| Output Signal Dampening | 0.3, 3.0, 10.0 Seconds | |
| Output Scaling (Pa) | -250 ~ 250 | 0 ~ 300 |
| -50 ~ 50 | 0 ~ 500 | |
| 0 ~ 50 | 0 ~ 1000 | |
| 0 ~ 100 | 0 ~ 1500 | |
| 0 ~ 150 | 0 ~ 2500 | |
Part Numbers & Options / Accessories
| PART NO | DESCRIPTION |
| ADPT | Air DP Transmitter (Multi-range) c/w Duct Kit |
Data Sheets
General specifications in .pdf format