Flamefast Gas Sensor (FGS)
The Flamefast Gas Sensor is one of the most versatile gas sensors available on the market.
With an Analogue and Relay output, as well as a BACnet MS/TP interface, FGS can connect directly into most third-party controllers or can easily connect to any of the Flamefast range of gas safety systems.
Top Key Features
- 24V AC/DC Power Supply
- Pre-calibrated
- Traffic light LCD readout
- Volt free contact output
- BACnet and Modbus
- UK Manufactured
Overview
The Flamefast Gas Sensor is one of the most versatile gas sensors available on the market.
With an Analogue and Relay output, as well as a selectable BACnet or Modbus interface, FGS can connect directly into most third-party controllers or can easily connect to any of the Flamefast range of gas safety systems.
In a large proportion of modern buildings, the plant room safety systems are BMS integrated, and the FGS has been designed with this in mind. It can be treated like any other field sensor, the latching facility allows direct integration with the primary safety circuit, then simply pulse the Digital Input, or reset over the network once the alarm has cleared.
The unit can also be fully configured by the Flamefast App using the USB interface, including the address, relay properties, alarm set points and LCD behaviour.
Key Features
- 24 AC/DC Power Supply
- Pre-calibrated
- Traffic light LCD readout
- Volt free contact output
- BACnet and Modbus
- Latching function with Reset Input
- Analogue output
- Simple configuration and calibration
- Calibration and ‘End of Life’ reminders
- Mounts onto any standard single gang junction box or conduit box
- UK MANUFACTURED
Dimensions
| Height: | 125 mm |
|---|---|
| Width: | 86 mm |
| Depth: | 36 mm |
Technical Specifications
| Power Supply: | 24V AC/DC ± 10% | ||||
|---|---|---|---|---|---|
| Power Consumption: | 100mA | ||||
| Output: | BACnet MS/TP and Modbus RTU Baud: 9600, Addresses: 32 Customisable through App with USB | ||||
| Analogue Outputs: | 0/2-10V Full scale linear | ||||
| VFC Output: | SPDT - 1A @ 24V Max | ||||
| Audible: | 60dB @ 30cm | ||||
| Operation Conditions: |
| ||||
| Sampling Method: | Diffusion | ||||
| Warm-up Time: | 60 Seconds (24 Hours for full stability) | ||||
| Response Time (T90): | < 60 Seconds (Adjustable) | ||||
| IP Rating: | IP40 | ||||
| Housing Material: | PC/ABS | ||||
| Colour: | Pure White (RAL9010) | ||||
| Approval: | CE, UKCA |
Installer Selectable Options
| Failsafe option | Energise/De-energise Relay |
| 0-10V or 2-10V | |
| Alarm Latching | Enable/Disable |
| Audible Alarm | Enable/Disable |
| THROUGH APP | |
| LCD Back Light | Enable/Disable |
| Auto Zero Calibration | Enable/Disable |
| Set-points | Alarm1 / Alarm 2 / Relay |
| Range | Analogue Output Scaling |
| Display | Gas Concentration / Formula |
| BACnet Properties | Identifier, Description, Location |
NEED THE REQUIREMENTS?

CommercialKitchens


TeachingAreas


Plant Rooms

Part Numbers & Options / Accessories
| Part No | Gas | Range | Typical Life (years) |
| FGS-NG | Natural Gas | 100% LEL | 5 |
| FGS-LPG | Propane | 100% LEL | 5 |
| FGS-H2 | Hydrogen (LEL) | 100% LEL | 5 |
| FGS-SF6 | Sulfur Hexafluoride | 1,000ppm | 5 |
| FGS-CO2 | Carbon Dioxide | 5% | 5 |
| FGS-CO | Carbon Monoxide | 200ppm | 5 |
| FGS-NO2 | Nitrogen Dioxide | 5ppm | 3 |
| FGS-NH3 | Ammonia | 100ppm | 3 |
| FGS-CL2 | Chlorine | 5ppm | 3 |
| FGS-H2e | Hydrogen (Electrochemical) | 1,000ppm | 3 |
| FGS-SO2 | Sulphur Dioxide | 5ppm | 3 |
| FGS-O2 | Oxygen | 25% | 5 |
OTHER GASES AVAILABLE ON REQUEST