GasMonitor

The New GasMonitor is a low cost, high specification Gas Detection controller for Laboratory installations in Universities, Hospitals and Research Facilities.

Top Key Features

  • New Stylish Enclosure
  • Selectable Ventilation Control Mode
  • Auto-reset following Fire Alarm
  • Auto-reset following Power Failure
  • Optional BACnet/Modbus module
  • 24VDC auxiliary power output
  • UK Manufactured

Overview

The New GasMonitor is a low cost, high specification Gas Detection controller for Laboratory installations in Universities, Hospitals and Research Facilities.

With an aesthetically pleasing housing, the ability to monitor up to 24 Flamefast Gas Sensors and relay outputs for remote monitoring or beacon activation, the GasMonitor is a self-contained system suitable for most laboratory installations, whilst the optional BACnet/ Modbus interface module allows multiple panels to be easily integrated with the onside BMS.

The addition of data logging provides the last 50 alarm conditions through the user interface, with a full even log available through the USB connection.

Key Features

  • New Stylish Enclosure
  • Selectable Ventilation Control Mode
  • Auto-reset following Fire Alarm
  • Auto-reset following Power Failure
  • Optional BACnet/Modbus module
  • 24VDC auxiliary power output
  • Interfaces for:
       - Thermal Links
       - Ventilation Systems
       - Remote Emergency Stop Buttons
       - Fire Alarm Systems
  • Remote reset interface
  • Relays for Alarm 1, Alarm 2, and Fault
  • 5 Year Warranty
  • UK MANUFACTURED

Dimensions

Height:180 mm
Width:180 mm
Depth:65 mm

Technical Specifications

Power Supply:85 ~ 300VAC 50/60Hz
Power Consumption:20W Max (Panel Only)
Power Output:
Gas Solenoid: Switched Mains
Alarm 1: SPDT - 5A @ 250V Max
Alarm 2: SPDT - 5A @ 250V Max
Fault: SPST - 5A @ 250V Max
BACnet MS/TP or Modbus RTU (with -COM)
Operation Conditions:
Temp: 0 ~ 50°C
Humidity: 0 ~ 95% (NC)
Body Material:PC/ABS
IP Rating:IP65
Colour:Pure White (RAL 9010)
Approval:CE, UKCA

External Device Interfaces

24V Out24V DC Power Out - 600mA (for TR, SS, FGS)
Gas SensorBACnet Interface for Gas Sensors
VentilationLV Signal to monitor external VFC
Thermal LinkLV Signal to monitor external VFC
Fire AlarmLV Signal to monitor external VFC
Remote StopLV Signal to monitor external VFC
Remote ResetLV Signal to monitor Momentary Switch

Installer Selectable Options

Ventilation ModeON / OFF
Fire Alarm Auto-resetON / OFF
Power Failure Auto-resetON / OFF

NEED THE REQUIREMENTS?

minReq-Kitchen

Commercial
Kitchens

arrow-kitchen
minReq-lab

Teaching
Areas

arrow-lab
minReq-plant

Plant 
Rooms

arrow-plant

Part Numbers & Options / Accessories

PART NODESCRIPTION
GM-P0-COMGasMonitor Panel +BACnet/Modbus Communication Module
  
FGS-O2Flamefast Gas Detector - Oxygen
FGS-CO2Flamefast Gas Detector - Carbon Dioxide
AVT24GTraffic Light Alarm Indicator - Grey
CABLE1Belden 8723 Equivalent (100m)

Data Sheets

General specifications in .pdf format

BIM Files

CAD drawings in .rfa format